Power Factor Calculator — PF and Reactive Power from kW and kVA

Calculator

A power factor calculator divides real power (kW) by apparent power (kVA) to get the power factor and uses √(kVA² − kW²) to find reactive power (kvar).

What is it

Power factor is the ratio of real power to apparent power; the closer to 1, the more efficiently power is used. A low power factor means more current for the same kW load, increasing losses and equipment sizing, and many commercial tariffs charge penalties for it. Real, apparent, and reactive power form a right triangle: kVA² = kW² + kvar².

PF = kW / kVA · reactive power kvar = √(kVA² − kW²)

How to use

  1. 1Enter real power in kW.
  2. 2Enter apparent power in kVA.
  3. 3Press calculate to see the power factor and reactive power.

Reference

Power Factor Calculator — PF and Reactive Power from kW and kVA Reference
Real powerApparent powerPower factorReactive power
80kW100kVA0.860kvar
90kW100kVA0.943.59kvar
95kW100kVA0.9531.22kvar

Sources & standards

FAQ

What is the power factor of an 80 kW, 100 kVA load?

PF = 80 / 100 = 0.8, and the reactive power is √(100² − 80²) = 60 kvar.

Why does power factor matter?

A low power factor draws more current for the same real power, increasing wiring losses and transformer sizing, and utilities often bill penalties below a threshold such as 0.9. Capacitor banks are a common correction.

Is power factor input sent to a server?

No. This calculator runs in your browser and does not send input to a server.